Q1T-00001-317
Q1T-00001-317 is TIME DELAY RELAYS manufactured by AMETEK.
- Part of the Q1T comparator family.
- Part of the Q1T comparator family.
1-8
TIME DELAY RELAYS
Delay On Make (Series Load)
Q1T Series
Features
- -
- -
- -
- -
100% functionally tested Solid state digital timing 20:1 maximum to minimum timing ratio pact size Low cost Superior transient protection Epoxy encapsulated Flame-retardant and solvent-resistant polyester thermoplastic housing
- Trimpot on-board with sealed cermet element
- File #E65038 Operating Logic: Upon application of input voltage, the time delay starts. At the end of the time delay, the load is energized. Reset is acplished by removing input voltage.
Note: The load may be located on either side of the line
SPECIFICATIONS
TIME DELAY Adjustment: On-board Trimpot Range: 50 ms to 10 hours in 9 ranges Repeatability: ±.5% +8 ms max. (0.25% typical) at constant temperature Accuracy: Maximum time -0%, +10%; Minimum time -30%, +0% INPUT Operating Voltage: 12, 24, 120, 240 VAC/DC ±10% (on DC models, unfiltered supply voltage must be full-wave rectified) Frequency: 50/60 Hz OUTPUT Type: Solid state normally open series load Rating: Maximum current -1 A AC/DC (resistive or inductive) Life: 100,000,000 operations PROTECTION Transient Voltage: Metal oxide varistor (see ratings below) Dielectric Breakdown: 3000 VAC, RMS, terminals to mounting Isolation Resistance: 100 megohms min. between terminals and case MECHANICAL Termination: .25” x .032” male fast-on terminals Mounting: Surface mount with one #8 screw ENVIRONMENTAL Storage Temperature: -40°C to 85°C Operating Temperature: -40°C to 65°C Humidity: 95% relative
.25 X .032 MALE FAST-ON TERMINALS (4 PL.)
.88 1.25 TIME DELAY ADJUSTMENT ACCESS 2.00 SQ.
LOGIC FUNCTION DIAGRAM
Input Voltage On Off On Off Timing
Load
Delay On Make Function
.170 DIA.
ORDERING INFORMATION
TIME RANGE .05 to 1 sec. .25 to 5 sec. .5 to 10 sec. 3 to 60 sec. 15 to 300 sec. 30 to 600 sec. 180 to 3600 sec. .5 to 10 hrs. TIME RANGE 24 to 480 sec. Reset time, during timing Reset time, after timeout Min. load Max. leakage current Voltage...