900,000+ datasheet pdf search and download

Datasheet4U offers most rated semiconductors data sheet pdf




Murata Manufacturing Electronic Components Datasheet

D1U4-W-1600-54-HB4C Datasheet

AC-DC Power Supply

No Preview Available !

www.murata-ps.com
D1U4-W-1600-54-HBxC
AC-DC Power Supply
FEATURES
1600W Output Power
1.6"(1U) x 14.0" x 4.0"
(41.0mm x 355.6mm x 101.6mm)
54VDC Main; PoE compatible
12V SB Output
PMBus™ Power Management Bus supported by
dual redundant I2C interfaces.
N+1 Redundancy Capable; hot swap (up to 8
modules in parallel)
Active current sharing on 54VDC Main output;
integral bidirectional MOSFET output isolation
device
Over-Voltage, Over-Current; Over-Temperature
Protection
Internal variable speed cooling fans
20ms full cycle hold up
RoHS Compliant
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at
www.murata-ps.com/en/3d/acdc.html
PRODUCT OVERVIEW
The D1U4-W-1600-54-HBxC is a 1600W power factor corrected (PFC) front end power module intended for hot swap
redundant systems. There is a main output of 54VDC (floating with respect to chassis ground) and a 12VDC Standby/
bias output (that is present whenever the incoming AC source is applied.
The form factor is suitable for 1RU chassis enclosures and is designed to deliver reliable bulk DC power to servers,
workstations, storage systems, PoE switches or any 54VDC distributed power architecture requiring high power
density.
The high efficiency design supports speed controlled dual DC fans in a thermally optimized package that is self-pro-
tecting and able to auto recover from over-current and over-temperature events. Visual status information is provided
via front panel mounted LED indicators in addition to hardware logic signals and a PMBus™ management interface.
ORDERING GUIDE
Model Number
Power Output High
Line AC
Power Output Low
Line AC
Main Output
Standby
Output
Airflow
D1U4-W-1600-54-HB4C
D1U4-W-1600-54-HB3C
1600W
1200W
Back to front
54V 12V
Front to back
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Current @ VIN = 200Vac
Maximum Current @ VIN = 90Vac
Inrush Current
Power Factor
Conditions
Ramp Up
Ramp Down
1600W
1200W
Cold start between 0 to 1ms
At 230Vac; FL
Min. Typ. Max.
90 115/230 264
47 50/60 63
81 89
70.5 78.0
10
15
100
0.95
Units
Vac
Hz
Vac
Arms
Apk
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Conditions
Min. Typ. Max. Units
Voltage Set Point
Line & Load Regulation
54V
52.38
55.62
Vdc
54V Output Current
0 30 A
Ripple Voltage & Noise1
20MHz Bandwidth
540 mVp-p
Load Capacitance
3800 24,000 μF
Voltage Set Point
Line & Load Regulation
12
Vdc
11.64
12.36
12V Output Current
0 2A
Ripple Voltage & Noise1
20MHz Bandwidth
33 mVp-p
Load Capacitance
1530 μF
1 Ripple and noise are measured with a parallel combination of a 0.1μF ceramic capacitor and 2 x 270μF OSCON
capacitors on each of the power module outputs measurement nodes. See test set up diagram below.
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com/support
CB
Test Certicate
and Test Report
PM
CPS_D1U4-W-1600-54-HBxC.A01 Page 1 of 6


Murata Manufacturing Electronic Components Datasheet

D1U4-W-1600-54-HB4C Datasheet

AC-DC Power Supply

No Preview Available !

RIPPLE MEASUREMENT
D1U4-W-1600-54-HBxC
AC-DC Power Supply
Power Supply
AC Phase
2x270uF OSCON
AC Ground
0.1uF Ceramic
Load Box
BNC to BNC Shielded Cable
General Notes:
1. Load the outputs at specified minimum
output current.
2. Connect the probe as shown with the
input tip and ground as short as possible.
3. Take all measurements
4. Repeat the measurements with the
outputs at specified maximum output
current.
Oscilloscope
20MHz BW
OUTPUT CHARACTERISTICS
Parameter
Remote Sense
Efficiency
Output Rise (Monotonic)
Startup Time
Transient Response
Current Sharing Accuracy (up to 8 in parallel)
Hot Swap Transients
Hold Up Time
Conditions
Min. Typ. Max.
Units
Remote sense is not enabled on these variants due to the System Control feature and the relatively wide line &
load regulation window.
230Vac (excluding fan)
90 %
10% to 95% rise time
Overshoot less than 10% for all outputs; no negative transition at
turn off.
AC Ramp Up
3s
PS_ON activation
250 ms
54VDC 50% step (50-100%; 100%-50%)
load; 1A/μs
12VSB 1A/μs
±2700
±250
mV
At 100% load
±10 %
5%
100% load 230Vac nominal
20
ms
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude
Shock
Operational Vibration
MTBF
Safety Approvals
Input Fusing
Weight
Conditions
Min. Typ. Max.
Non-Condensing
-40 70
0 50
Non-Condensing
10 90
5 90
3000
Non-Operating
30
Operational, 0.5G; 5-500Hz
Telcordia SR-332 40°C
630
CAN/CSA-C22.2 No.60950-1-07 Am 1:2011
ANSI/UL 60950-1-2011
IEC60950-1:2005 (2nd Ed)+A1:2009 and EN60950-1:2006/A11:2009/A1:2010/A12:2011
CQC GB4943,1-2011
Internal 20A/250V rated fast blow in AC line
4.63/2.1
Units
°C
%
M
G
K Hours
lbs/kg
www.murata-ps.com/support
CPS_D1U4-W-1600-54-HBxC.A01 Page 2 of 6


Part Number D1U4-W-1600-54-HB4C
Description AC-DC Power Supply
Maker Murata Power Solutions
PDF Download

D1U4-W-1600-54-HB4C Datasheet PDF






Similar Datasheet

1 D1U4-W-1600-54-HB4C AC-DC Power Supply
Murata Power Solutions





Part Number Start With

0    1    2    3    4    5    6    7    8    9    A    B    C    D    E    F    G    H    I    J    K    L    M    N    O    P    Q    R    S    T    U    V    W    X    Y    Z

Site map

Webmaste! click here

Contact us

Buy Components

Privacy Policy