Liquid Level Control Systems
ES825-100F/XF/CF Leak Sensors
Installation Instructions
Sensor Model
ES825-100F
ES825-100XF (Extended Temperature)
ES825-100CF (Chemical Resistant)
Non-Discriminating Leak Sensor
w/Supervised Wiring and
Fault Detection, 24 VDC
For use with the
following consoles:
LC2000
TMS3000
TMS2000
NOTE: ES825-100 SERIES SENSORS ARE NOT COMPATIBLE
WITH Wireless DATA ACQUISITION MODULE (WiDAM) USED
IN CONJUNCTION WITH WIRELESS CONSOLES. REFER TO
THE ES825-300 SERIES.
Bulletin 142 Rev. E (04/09/10)
© COPYRIGHT 2010 PNEUMERCATOR CO., INC.
TEL: (631) 293-8450
FAX: (631) 293-8533
WEBSITE: www.pneumercator.com
PNEUMERCATOR TECHNICAL SUPPORT
1 (800) 209-7858
2/22/2013 12:54:35 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.
Page 1 of 4




PNEUMERCATOR

ES825-100F Datasheet Preview

ES825-100F Datasheet

Leak Sensors

No Preview Available !

PRODUCT DESCRIPTION: Model ES825-100F is a solid-state, electronic leak sensor utilizing
electo-optic technology to detect the presence of liquids in secondary containment applications. The "X"
version includes all the features of the standard ES825-100F, with operation over an extended temperature
range. The "C" version includes all the features of the standard ES825-100F and the "X" version, with the
addition of a chemical-resistant sensor body and cable compatible with most acids, alkalines and solvents.
The sensors contain no moving parts, are unaffected by vapors, and due to their compact size are ideal for
interstitial spaces. When connected with a LC2000 or TMS series controller, they support Pneumercator's
FAULT-DETECT supervised wiring technology, which automatically detects sensor or field wiring faults.
APPLICATIONS: Sensors can be installed for leak detection in containment, manway and piping sumps,
dry annular space in double-wall tanks, dispenser pans or turbine enclosures. The model selected for each
application depends on its compatibility with the stored product.
SPECIFICATIONS:
MODEL NO. WETTED MATERIALS
ES825-100F *
ES825-100XF *
POLYSULFONE, POLYPROPYLENE,
PVC & EPOXY
POLYSULFONE, POLYPROPYLENE,
PTFE (TEFLON®) & EPOXY
ES825-100CF *
POLYPROPYLENE,
PTFE (TEFLON®) & EPOXY
OPERATING TEMP.
CABLE
-4°F TO +176°F
(-20°C TO +80°C)
22 AWG, 3-CONDUCTOR,
PVC JACKET, 25' LONG
-40°F TO +176°F
(-40°C TO +80°C)
22 AWG, 3-CONDUCTOR,
PTFE (TEFLON®) JACKET,
20' LONG
TECHNOLOGY
ELECTRO-OPTIC,
NO MOVING PARTS
* Approved for UL Class I, Div 1, Groups C and D hazardous locations when used in conjunction with the TMS series controllers.
.62"
(HEX FLAT)
3.00"
CABLE LENGTH
PULL RING REMOVED
3 CONDUCTOR CABLE
PASS-THRU OPENING SIZE
3/4" NPT MINIMUM
REMOVABLE
PULL RING
SHRINK TUBE
("C" & "X" VERSIONS ONLY)
CONVOLUTIONS ACCEPTS 1/2" ENT
1/4" NPT
INSTALLATION: Sensor may be suspended by its cable, placed on the containment or sump floor, or
thru-wall mounted via a 1/4" FNPT opening. Two methods are available when installing in a dry annular space.
The first uses a fish tape and pull string, the second uses a section of 1/2" ENT Flex Conduit attached to the
sensor. Pneumercator recommends that sensor should be installed in an area where there is MINIMAL
exposure to ambient light.
METHOD 1
1. If tank has an existing pull string, skip steps
2 & 5.
2. Insert Fish Tape through annular space.
3. Attach Pull String to sensor.
4. Tag pull string and cable each 16 feet (for
tank diameter up to 10 feet) from sensor.
5. Attach fish tape to pull string.
6. Pull sensor through annulus.
7. Match tag mark on cable and pull string.
8. Sensor now positioned on the bottom
centerline of tank.
METHOD 2
1. Pull sensor cable through Flex Conduit and insert
sensor's back end.
2. Tag conduit at the distance for your tank dia.
3. Feed sensor through annulus.
4. Stop when tag mark is at the top of annulus.
5. Sensor now positioned on the bottom centerline of tank.
TAG MARK
ON CONDUIT
1/2" ENT FLEX
CONDUIT
SENSOR
CABLE
PULL STRING
Bulletin 142 Rev. E (04/09/10)
2/22/2013 12:54:36 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.
TAG MARKS:
Ø4" = 75", Ø6" = 115", Ø8" = 150",
Ø10" = 190", Ø12" = 225"
Page 2 of 4


Part Number ES825-100F
Description Leak Sensors
Maker PNEUMERCATOR
Total Page 4 Pages
PDF Download

ES825-100F Datasheet PDF

View PDF for Mobile








Similar Datasheet

1 ES825-100CF Leak Sensors
PNEUMERCATOR
2 ES825-100F Leak Sensors
PNEUMERCATOR
3 ES825-100XF Leak Sensors
PNEUMERCATOR





Part Number Start With

0    1    2    3    4    5    6    7    8    9    A    B    C    D    E    F    G    H    I    J    K    L    M    N    O    P    Q    R    S    T    U    V    W    X    Y    Z

Site map

Webmaste! click here

Contact us

Buy Components

Privacy Policy