Datasheet4U Logo Datasheet4U.com

3UA6230 - Relays

📥 Download Datasheet

Full PDF Text Transcription (Reference)

The following content is an automatically extracted verbatim text from the original manufacturer datasheet and is provided for reference purposes only.

View original datasheet text
I Operating Instructions C.T. Operated Bimetal Relay with single phasing protection feature Type 3UA62 30  Warning: Hazardous Voltage can cause Electric Shock and burns. Disconnect Power before proceeding with any work on this equipment Table 1 Type Min Setting “AMP” 3UA62 30 85 115 160 200 250 Max. Setting “AMP” 135 180 250 320 400 Fuse rating type 3NA1 “AMP” 224 250 355 400 500 Load current corresponding to marking 0.625/0.63 0.7 0.8 “AMP” 0.9 1.0 85 94.5 108 121.5 135 115 126 144 162 180 160 175 200 225 250 200 224 256 288 320 250 280 320 360 400 The Siemens 3UA62 30 current transformer operated bi-relays provide accurate overload and accelerated single phasing protection for three phase motors having rated currents upto 400A.