900,000+ datasheet pdf search and download

Datasheet4U offers most rated semiconductors data sheet pdf






celduc

SIB865970 Datasheet Preview

SIB865970 Datasheet

AC Semiconductor Contactor

No Preview Available !

celpac®
AC Semiconductor Contactor
pitch 45mm
compact size and DIN rail mounting.
t Ready to use Two-Phase Relay: " Install it & Forget it!"
t Zero cross model : 24-510VAC 50A
back to back thyristors on output -
TMS2 technology - I2t value > 1500A2s
t Plage de contrôle : 150-240VAC/DC .
LED de visualisation sur l'entrée de couleur verte.
t Very high immunity : Voltage protection on output
and input- 4kV according IEC61000-4-4 & 5
t IP20 housing
t Low leakage current (<1mA) and low zero cross
voltage .
t Mounting and dismounting on DIN rail without any
tool or directly mountable on panel.
t Designed in conformity with EN60947-4-3
(IEC947-4-3) and EN60950
-UL-cUL
http://www.DataSheet4U.net/
Dimensions :
S/CLP/SIB865970/B/21/04/2004
page 1 / 4GB
SIB865970
Output : 24-510VAC 2x22A(*)
2 Inputs : 150-240VAC/DC
(*) see conditions (thermal curve page 3)
2 x18A
3x 400VAC
Proud to serve you
All technical caracteristics are subject to change without previous notice.
Caractéristiques sujettes à modifications sans préavis.
Typical
Protection
application:
L1 L2
12kW resistor
(AC-51 load)
on 400 VAC
The two input
control must be
mounted in
parallel for
230VAC
or can be mounted
in serie for
400VAC input.
T1 T2
A2 A1
Control
A2 A1
Control
LOAD /CHARGE
celduc
relais
datasheet pdf - http://www.DataSheet4U.net/




celduc

SIB865970 Datasheet Preview

SIB865970 Datasheet

AC Semiconductor Contactor

No Preview Available !

celpac®
S/CLP/SIB865970/B/21/04/2004
page 2 / 4GB
Control characteristics (at 25°C)
for each input :
Paramètre / Parameter
Control voltage : AC control
Control voltage : DC control
Control current (@ Uc )
Release voltage
Input LED
Input immunity : EN61000-4-4
Input immunity : EN61000-4-5
inputs in parallel for 230VAC or in serie fo 400VAC control
DC
Symbol Min Nom Max Unit
8
Input : Ic = f( Uc)
Uc 150 230 240 VAC
Uc 110
240 VDC
Ic 3
7 mA
6
4
Uc off 15
green
V2
2kV
2KV
0
0
50 100 150 200 250
U c (V)
Output characteristics (at 20°C)
Parameter for each way
Load voltage
Operating range
Peak voltage
Clamping voltage
Zero cross level
Latching voltage
AC-51 nominal current : permanent
AC-53 nominal current
Non repetitive overload current
On state voltage drop (typical value)
Dynamic resistance (typical value)
Output Power dissipation (typical value) : for each way ( ==> x2)
Thermal resistance between junction to air
Off state leakage current
Minimum load current
Turn on time
Turn off time
Operating frequency range
Off state dv/dt
Maximum di/dt non repetitive
I2t (<10ms)
Conducted immunity level
Conducted immunity level
Short circuit protection
Conditions
Ie nom
( see Fig. 2 page 3)
tp=10ms (Fig. 3)
@ 25°C
Symbol
Ue
Uemin-max
Up
Uclamp
Usync
Ua
Ie AC-51
Ie AC-53
Itsm
Vt
rt
Pd
Typ.
400
24-510
1200
820 (@1mA)
20
8
2 x 22
2 x 12
550
0,9
8
0,81xIe+0,08xIe2
Unit
V rms
V rms
V
V
V
V
A rms
A rms
A
V
m
W
@Ue, 50Hz
http://www.DataSheet4U.net/
Uc nom DC ,f=50Hz
Uc nom DC ,f=50Hz
IEC 1000-4-4 (burst)
IEC 1000-4-5(schocks)
FERRAZ
Rthj/a
2,2 (1,8)
K/W
Ilk <1 mA
Iemin
5 mA
ton max
30
ms
toff max
30
ms
f
0,1-440
Hz
dv/dt
500 V/µs
di/dt 50 A/µs
I2t
1500
A2s
4kV criterion A
4kV criterion A
gRC 25A/32A/50A/63A 14x51
General characteristics (at 20°C)
Input to output insulation
Output to case insulation
Insulation resistance
Rated impulse voltage
Protection level / CEI529
Pollution degree
Vibration resistance 10 -55 Hz according to CEI68 :
Shocks resistance according to CEI68 ( on DIN rail / with screws)
Ambient temperature (with no icing or condensation)
Storage temperature (with no icing or condensation)
Ambient humidity
Weight
Conformity
Conformity
Ui
Ui
Ri
Uimp
-
-
double amplitude
-
-
HR
4000
4000
100 (@500VDC)
4000
IP20
2
1,5
30/50
-30 /+80
-30/+100
40 to 85
450
EN60947-4-3 (IEC947-4-3)
EN60950 UL/cUL pending
VRMS
VRMS
M
V
mm
g
°C
°C
%
g
celduc
relais
www.celduc.com
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE E-Mail : celduc-relais@celduc.com
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19
datasheet pdf - http://www.DataSheet4U.net/


Part Number SIB865970
Description AC Semiconductor Contactor