180-JC6DT3
180-JC6DT3 is DIESEL ENGINE-GENERATOR SET manufactured by MTU Onsite Energy.
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 180-JC6DT3 180 ek W 60 Hz Standby
/ / 160 ek W / 60 Hz / Prime
- 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz k W k VA AMPS sk VA@30% Voltage Dip Generator Model- Temp Rise Connection 240V-
- 1 1.0 60 180 180 750 267 432CSL6210 130°C/27°C
12 LEAD ZIG-ZAG
240V-
- 1 1.0 60 180 180 750 370 432PSL6228 130°C/27°C 4 LEAD
208V-
- 3 0.8 60 180 225 625 370 431CSL6206 130°C/27°C
12 LEAD LOW WYE
240V-
- 3 0.8 60 180 225 541 370 431CSL6206 130°C/27°C
12 LEAD HI DELTA
480V-
- 3 0.8 60 180 225 271 370 431CSL6204 130°C/27°C 12 LEAD HI WYE
600V-
- 3 0.8 60 180 225 217 378 431PSL6242 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz k W k VA AMPS sk VA@30% Voltage Dip Generator Model- .. Temp Rise Connection 240V 1 1.0 60 160 160 667 267 432CSL6210 105°C/40°C
12 LEAD ZIG-ZAG
240V 1 1.0 60 160 160 667 370 432PSL6228 105°C/40°C 4 LEAD
208V 3 0.8 60 160 200 555 370 431CSL6206 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 160 200 481 370 431CSL6206 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 160 200 241 370 431CSL6204 105°C/40°C 12 LEAD HI WYE
600V 3 0.8 60 160 200 192 378 431PSL6242 105°C/40°C 4 LEAD WYE
- The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
- - UL2200 Offered
// / /
Facts
// // // // // // // // // //
EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and factory tested MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty Custom Design for Any Application 6068HF485 Diesel...