• Part: NJYB3
  • Description: Relay
  • Manufacturer: CHiNT
  • Size: 117.73 KB
Download NJYB3 Datasheet PDF
CHiNT
NJYB3
NJYB3 is Relay manufactured by CHiNT.
Relay Protection Relay 2. Type designation N JYB 3 - - 1~16 function code Design sequence No. Relay pany code NJYB3 Relay 1. General NJYB3 relay is used to provide overvoltage, undervoltage, phase failure, phase sequence and threephase unbalance control in three-phase three-wire 380V circuits and three-phase four-wire 220V circuits with a frequency of AC 50Hz. For example, it is used for power control systems, air conditioning systems and motors. This relay is a voltage protection relay. After detecting the voltage signal, the relay processes the input signal, judges if there is an overvoltage, undervoltage, phase failure, error-phase or unbalance and controls the operation accurately and stably by means of the built-in microprocessor. 3. Technical data Model NJYB3 Protection function Protection operation time Rated operational voltage Contact capacity Contact form Usage category Conventional heating current (Ith) Electrical Mechanical life life Overvoltage Undervoltage Three-phase voltage unbalance Phase failure, phase sequence 0.1s~10s ≤1s Three-phase three-wire system: Resistive load: AC 380V 50Hz AC250V 6A cosφ=1 Three-phase four-wire system: AC 220V 50Hz Inductive load: AC250V 1A cosφ=0.4 1 N/O, 1 N/C AC-15 3A 105 106 > >>...