TAD4x00AxA
Description
Cable/bus-bar type current transformer with DIN-rail/busbar and panel mounting facility. Rated primary currents from 100 A to 2000 A.
Ordering Key
Model Primary current Secondary current
TAD4 200A 5A
Type Selection
Model TAD4: Cable diameter: max. 32 mm Bus-bar size: 32 x 16 mm 41 x 11 mm Primary current Refer to Range Table TAD6: Cable diameter: max. 52 mm Bus-bar size: . 55 x 22 mm 65 x 20 mm
Data Shee
Input Specifications
Operating frequency Max. system voltage Rated insulation level Short-time current rating Ith Idyn 40 to 60 Hz 0.72 k V 3 k V / 1 min. @ 50 Hz Typical 100 In / 1 s 2.5 Ith The short-time thermal current Ith is anyway limited by the cable/bus-bar size 120% ≤5
General Specifications
Standards Housing Mounting According to IEC 60185 ABS, self-extinguishing: UL 94 V-0 DIN-rail 46277/bus-bar and panel mounting (brackets supplied with the CT) Screws + washers for secondary terminals Brackets for panel mounting Screws for cable/bus-bar mounting Sealable...