Datasheet4U Logo Datasheet4U.com

SCM7B32 - Isolated Process Current/Voltage Input Modules

General Description

The SCM7B32 current input modules accept input signals in the 4-20mA or 0-20mA ranges from the field and provide a high-level output to the process control system (Figure 1).

Current to voltage conversion occurs internal to the module, which is factory calibrated to ensure the highest accuracy.

Key Features

  • Accepts Current or Voltage Input.
  • Provides High-Level Voltage Outputs.
  • 1500Vrms Transformer Isolation.
  • Accuracy, ±0.03% of Span Typical, ±0.1% Max.
  • ANSI/IEEE C37.90.1 Transient Protection.
  • Input Protected to 120Vrms Continuous.
  • Noise, 500µVp-p (5MHz), 300µVrms (100kHz).
  • 105dB CMRR.
  • Easy DIN Rail Mounting.
  • CSA C/US Certified.
  • CE and ATEX Compliant Figure 1: SCM7B32/33 Block Diagram 72 For inform.

📥 Download Datasheet

Datasheet Details

Part number SCM7B32
Manufacturer Dataforth
File Size 223.67 KB
Description Isolated Process Current/Voltage Input Modules
Datasheet download datasheet SCM7B32 Datasheet

Full PDF Text Transcription for SCM7B32 (Reference)

Note: Below is a high-fidelity text extraction (approx. 800 characters) for SCM7B32. For precise diagrams, and layout, please refer to the original PDF.

Isolated Process Control Signal Conditioning Products SCM7B SCM7B32/33 Isolated Process Current/V oltage Input Modules Description The SCM7B32 current input modules accep...

View more extracted text
tage Input Modules Description The SCM7B32 current input modules accept input signals in the 4-20mA or 0-20mA ranges from the field and provide a high-level output to the process control system (Figure 1). Current to voltage conversion occurs internal to the module, which is factory calibrated to ensure the highest accuracy. SCM7B33 voltage input modules accept input signals in the +1V to +5V or 0 to +5V ranges from the field and provide a high-level output to the process control system. As an alternative, the SCM7B33 can be used with an external 250Ω resistor (Dataforth SCM7BXR1 or equivalent), to accept input signals in