FCPS-2404
FCPS-2404 is NAC Power Expander manufactured by Fire Lite.
FEATURES
- 4 amps total of continuous current available.
- One 24 VDC Style Y (Class B) NAC.
- One optically-isolated input/control circuit, patible with 12 VDC and 24 VDC control panel.
- External Strobe Synchronization could be added with UL listed synch module, which can be housed in the FCPS2404.
- Can be wired daisy-chain style.
- Self-contained in pact, lockable cabinet (15" [381 mm] H x 14.5" [368 mm] W x 3.050" [775 mm] D).
- Output is filtered and pletely power limited.
- Integrated supervised battery charger for lead acid or gel type batteries.
- Uses only 7 AH (Amp Hour) batteries
- can be acodated in the power supply cabinet.
- NAC supervised by host FACP.
- Earth fault detection by host FACP.
- Fixed terminal blocks for field wiring capable of accepting 12
- 22 AWG wire.
- AC fail Form-C relay contacts (fail-safe).
- Battery/Charger trouble Form-C relay contacts (fail safe).
- Optional hardware kit #90273 to be used when installing addressable or synchronization modules.
Important: Do not use shielded wire for Control Input Circuit. NAC Output Circuit
- TB3, Terminals 3 (+) & 4 (- ) alarm polarity
- Voltage Rating: 24 VDC.
- Current: 4 amps maximum total continuous current.
- Style Y (Class B)
- requires End-of-Line Resistor from circuit connected to input.
- Refer to Fire- Lite Device patibility Document for listed patible devices.
LED INDICATORS
- AC power on (green) LED.
- Battery/Charger trouble (yellow) LED.
SPECIFICATIONS
Primary (AC) Power
- TB1
- 120 VAC 50/60 Hz, 1.45 amps maximum.
- Wire size: minimum #14 AWG (2 mm²) with 600V insulation. Control Input Circuit
- TB3, Terminals 1 (+) & 2 (- ) alarm polarity
- Trigger Input Voltage: 9 to 32 VDC.
- Input Current Draw in Alarm Polarity: 16
- 32 volts, 10 m A maximum. 9 -16 volts, 4 m A maximum.
Important: Do not use shielded wire for NAC Output Circuit. AC Fail Relay Contact Rating
- TB6
- Fail-safe relay (normally energized, transfers with loss of...