The MMI-6SF connects to the signaling line circuits (SLC) of the FCI analog addressable series fire alarm control panels. Each of the MMI-6SF initiating device circuits occupies its own address on the system’s SLC allowing each to be fully programmable in its control-by-event sequence of operation. The address of the first initiating device circuit is set with a pair of rotary dials.
Part No. MMI-6SF
Datasheet MMI-6SF Download
Manufacturer
Gamewell-FCI
Description Multi-Mod 6 zone interface module
Buy Stock & Price
MMI-6SF datasheet page 1 preview

DESCRIPTION

The Velociti™ Series, multi-mod six zone interface module (MMI-6SF) provides six (6), Style B (Class B) or three (3), Style D (Class A) supervised initiating device circuits (IDC) suitable for use with U. L. Listed conventional 2-wire smoke detectors as well as any normally open contact device. The VelocitiTM Series use a communication protocol that substantially increases the speed of communication between the sensors and certain FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. Each remaining circuit is automatically assigned to its own subsequent address. The MMI-6SF module includes an address disable jumper matrix to allow a maximum of two unused addresses to be turned off to free these addresses for other purposes.