Datasheet4U Logo Datasheet4U.com

MM-1315-100 - filter

📥 Download Datasheet

Datasheet Details

Part number MM-1315-100
Manufacturer JMK
File Size 78.04 KB
Description filter
Datasheet download datasheet MM-1315-100 Datasheet

Full PDF Text Transcription (Reference)

The following content is an automatically extracted verbatim text from the original manufacturer datasheet and is provided for reference purposes only.

View original datasheet text
The Mm-1315-100 filter is designed for use with large computer or motor installations where heavy current is drawn continuously. This filter can handle large in-rush current typical of modern power supplies. When data lines or power is shared with other systems the ground coil helps breakup ground loops which can cause system errors and also increase conducted RF MM-1315-100 Operating Voltage = 250/480 V~, 50 / 60 Hz Operating Voltage = 125/208 V~, 50 – 400 Hz Operating Current = 100 A / Phase Temperature Range = -20 TO 50 Deg. C Diel. Withstand (L-CASE) =1500 V~For 1 MIN. Diel. Withstand (L-L) = 2200 Vdc For 1 Min. Leakage Current = 18 ma (max) @ 250 V~, 60 Hz Resid.Volt after 3.0 second = 20 V Max. Max. Cap. each line to case = 0.