Click to expand full text
Voltage Transducer DCVT 1000/SP1
For the electronic measurement of DC voltages with a galvanic isolation between the primary circuit (high voltage) and the secondary circuit (electronic circuit).
VPN = 1000 V
Preliminary
All Data are given with a R L = 10 k Ω
Electrical data
VPN VPmax VP RP RL VOUT Primary nominal voltage Primary voltage measuring range Not measurable overload Primary input resistance Load impedance Output voltage 1) 1000 V DC 56 .. 1400 V DC 3000 (1s/h) VDC appr. 97.5 MΩ 10 kΩ VOUT = a x VP - b V a = 0.01 ± 0.5 % b = 0.3 ± 0.1 appr. 1 mA/kV 5.5 kV 2.2 kV
Features
• Self-Powered • Insulated plastic case recognized
according to UL 94-V0
• Included primary resistor
IC Vd Ve
Current consumption R.m.s. voltage for AC isolation test, 50 Hz,1 min R.m.s.