Datasheet4U.com

HAS400-P Datasheet PDF

LEM HAS400-P

Current Transducer

Part No. HAS400-P
Datasheet HAS400-P Download
Manufacturer
LEM
Description Current Transducer
Buy Stock & Price
HAS400-P datasheet page 1 preview

FEATURES

● Hall effect measuring principle
● Insulating plastic case made of polycarbonate PBT recognized according to UL 94-V0. Advantages
● Easy mounting
● Low power consumption
● Small size and space saving
● Only one design for wide current ratings range
● High immunity to external interference. εtot Total error @ IP N, TA = 25 °C (excluding offset) < ±1 % of IP N εL Linearity error 2) (0 ... ±IP N) < ±1 % of IP N UO E Electrical offset voltage, TA = 25 °C < ±20 mV UO H Hysteresis offset voltage @ IP = 0, after an excursion of 1 × IP N < ±20 mV TCUO E Temperature coefficient of UO E HAS 50-P < ±2 mV/K HAS 100 ... 600-P < ±1 mV/K TCUout Temperature coefficient of Uout (% of reading) tD 90 Delay time to 90 % of IP N 3) BW Frequency bandwidth 4) (small signal, −3 dB) < ±0.1 %/K < 3 µs DC ... 50 kHz General data

APPLICATIONS

● AC variable speed drives
● Static converters for DC motor drives
● Battery supplied applications
● Uninterruptible Power Supplies (UPS)
● Switched Mode Power Supplies (SMPS)
● Power supplies for welding applications.
HAS400-P page 2 preview HAS400-P page 3 preview