Datasheet4U Logo Datasheet4U.com

LF505-S - Current Transducer

Key Features

  • Closed loop (compensated) current transducer using the Hall effect.
  • Insulating plastic case recognized according to UL 94-V0. Special features.
  • IPM = 0 … ±1480 A.
  • UC = ±24 V (±5 %) UC.
  • Connection to secondary circuit on JST BH03B-XASK-BN connector UC.
  • 2D Datamatrix Barcode-label.
  • Improved dynamic performance.
  • Extended temperature range. Advantages.
  • Excellent accuracy.
  • Very good linearity.

📥 Download Datasheet

Datasheet Details

Part number LF505-S
Manufacturer LEM
File Size 417.20 KB
Description Current Transducer
Datasheet download datasheet LF505-S Datasheet

Full PDF Text Transcription (Reference)

The following content is an automatically extracted verbatim text from the original manufacturer datasheet and is provided for reference purposes only.

View original datasheet text
Current Transducer LF 505-S/SP27 For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. dCl dCp IPN = 500 A Electrical data IPN Primary nominal rms current IPM Primary current, measuring range RM Measuring resistance with ±24 V @ ±500 A max @ ±1480 A max ISN Secondary nominal rms current KN Conversion ratio UC Supply voltage (±5 %) IC Current consumption IP Accuracy - Dynamic performance data 500 A 0 … ±1480 A R R M min M max 0 148.5 Ω 0 2.5 Ω 100 mA 1 : 5000 ±24 V 33 + IS mA IS RM X Accuracy @ IPN, TA = 25 °C ±0.6 @ IPN, TA = −10 °C … +70 °C ±0.9 εL Linearity error < 0.