SL1026A700 - Gas Plasma Arrester

Download the SL1026A700 datasheet PDF. This datasheet also covers the SL1026A275 variant, as both devices belong to the same gas plasma arrester family and are provided as variant models within a single manufacturer datasheet.

Key Features

  • RoHS compliant.
  • 55 kA surge capability (single shot) tested with 8/20 S pulse as defined by IEC 61000-4-5.
  • 40 kA surge capability (repetitive).
  • Will protect against Trapezoidal waveforms as specified in RIA 12.
  • Will protect against capacitor discharge voltage transient waveforms as specified in RIA 12.
  • Will protect against double exponential voltage transient waveforms as specified in IEC 571.

📥 Download Datasheet

Note: The manufacturer provides a single datasheet file (SL1026A275-Littelfuse.pdf) that lists specifications for multiple related part numbers.

Full PDF Text Transcription (Reference)

The following content is an automatically extracted verbatim text from the original manufacturer datasheet and is provided for reference purposes only.

View original datasheet text
Heavy Duty Delta Range RoHS Pb Greentubeā„¢ SL1026 Series Gas Plasma Arrester The SL1026 series is a heavy-duty transient suppresser using Gas Plasma technology. In response to a transient voltage which exceeds the fixed breakover voltage (selected according to part number) the device changes from a very high impedance state to a low impedance state, there by conducting harmful current away from the protected system. The design is optimized for the protection of electrical and electronic equipment employed in Railway systems: carefully designed geometry ensures the device does not become a short circuit in the event of a failure due to conditions and events beyond the design criteria. An electrical mounting clip (PN SL1053 ) is available to aid mounting and connection.