Datasheet4U Logo Datasheet4U.com

1750-XC6DT2 - DIESEL ENGINE-GENERATOR SET

📥 Download Datasheet

Datasheet Details

Part number 1750-XC6DT2
Manufacturer MTU Onsite Energy
File Size 538.87 KB
Description DIESEL ENGINE-GENERATOR SET
Datasheet download datasheet 1750-XC6DT2 Datasheet

Full PDF Text Transcription (Reference)

The following content is an automatically extracted verbatim text from the original manufacturer datasheet and is provided for reference purposes only.

View original datasheet text
A tognum Group Brand DIESEL ENGINE-GENERATOR SET 1750-XC6DT2 1750 ekW  60 Hz  Standby /  /  1600 ekW / 60 Hz / Prime 480 - 4160V System Ratings Standby Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 480V** 3 0.8 60 1750 2187.5 2631 4700 743RSL4052 130°C/27°C 4 BAR WYE 600V** 3 0.8 60 1750 2187.5 2105 3600 744RSS4292 125°C/40°C 4 LEAD WYE 4160V 3 0.8 60 1750 2187.5 304 4000 743FSM4370 130°C/27°C 6 LEAD WYE Prime Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 480V 3 0.8 60 1600 2000 2406 4700 743RSL4052 105°C/40°C 4 BAR WYE 600V 3 0.