Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130°C Standby Temperature Rise 1 Bearing, Sealed Flexible Coupling Full Amortisseur Windings 125% R.
The following content is an automatically extracted verbatim text
from the original manufacturer datasheet and is provided for reference purposes only.
View original datasheet text
A tognum Group Brand
Diesel Engine-Generator Set 250-XS6DT3
250 ekW / 60 Hz / Standby 208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model Temp Rise Connection
** UL2200 Offered
240V** 1 1.0 60 250 250 1042 450 572RSL4025 130°C/27°C 12 LEAD ZIG-ZAG
208V** 3 0.8 60 250 312.5 867 520 432CSL6210 130°C/27°C 12 LEAD LOW WYE
240V** 3 0.8 60 250 312.5 752 520 432CSL6210 130°C/27°C 12 LEAD HI DELTA
480V** 3 0.8 60 250 312.5 376 700 432CSL6210 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 250 312.