Datasheet Summary
A tognum Group Brand
GAS Engine-Generator Set 40-GC6NLT1 40 ekW 60 Hz Standby
/ /
- 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz Natural Gas Ratings: Amps Natural Gas Ratings: kW/kVA LP Gas Ratings: Amps LP Gas Ratings: kW/kVA skVA@30% Voltage Dip Generator Model- Temp Rise Connection 240V-
- 1 1.0 60 146 35/35 167 40/40 128 362CSL1604 130°C/27°C
12 LEAD ZIG-ZAG
240V-
- 1 1.0 60 146 35/35 167 40/40 102 284CSL1550 125°C/40°C
4 LEAD
208V-
- 3 0.8 60 139 40/50 139 40/50 93 284CSL1542 130°C/27°C
12 LEAD LOW WYE
240V-
- 3 0.8 60 120 40/50 120 40/50 93 284CSL1542 130°C/27°C
12 LEAD HI DELTA
480V-
- 3 0.8 60 60...