60-JC6DT3
60-JC6DT3 is DIESEL ENGINE-GENERATOR SET manufactured by MTU Onsite Energy.
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 60-JC6DT3 60 ek W 60 Hz Standby
/ / 55 ek W / 60 Hz / Prime
- 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz k W k VA AMPS sk VA@30% Voltage Dip Generator Model- Temp Rise Connection 240V-
- 1 1.0 60 60 60 250 119 362CSL1604 130°C/27°C
12 LEAD ZIG-ZAG
240V-
- 1 1.0 60 60 60 250 130 361CSL1613 130°C/27°C 4 LEAD
208V-
- 3 0.8 60 60 75 208 150 361CSL1602 130°C/27°C
12 LEAD LOW WYE
240V-
- 3 0.8 60 60 75 180 150 361CSL1602 130°C/27°C
12 LEAD HI DELTA
480V-
- 3 0.8 60 60 75 90 198 361CSL1602 130°C/27°C 12 LEAD HI WYE
600V-
- 3 0.8 60 60 75 72 136 361PSL1633 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz k W k VA AMPS sk VA@30% Voltage Dip Generator Model- .. Temp Rise Connection 240V 1 1.0 60 55 55 229 119 362CSL1604 105°C/40°C
12 LEAD ZIG-ZAG
240V 1 1.0 60 55 55 229 130 361CSL1613 105°C/40°C 4 LEAD
208V 3 0.8 60 55 68.75 191 150 361CSL1602 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 55 68.75 165 150 361CSL1602 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 55 68.75 83 140 361CSL1602 105°C/40°C 12 LEAD HI WYE
600V 3 0.8 60 55 68.75 66 136 361PSL1633 105°C/40°C 4 LEAD WYE
- The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
- - UL2200 Offered
// / /
Facts
// // // // // // // // // //
EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and factory tested MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty Custom Design for Any Application 5030HF285 Diesel...