900-XC6DT2
900-XC6DT2 is DIESEL ENGINE-GENERATOR SET manufactured by MTU Onsite Energy.
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 900-XC6DT2 900 ek W 60 Hz Standby
/ / 800 ek W / 60 Hz / Prime
- 4160V
System Ratings
Standby
Voltage (L-L) Phase PF Hz k W k VA AMPS sk VA@30% Voltage Dip Generator Model- Temp Rise Connection 208V-
- 3 0.8 60 900 1125 3123 2600 741RSL4045 130°C/27°C 12 LEAD LOW WYE 240V-
- 3 0.8 60 900 1125 2706 2600 741RSL4045 130°C/27°C 12 LEAD HI DELTA 480V-
- 3 0.8 60 900 1125 1353 2600 574RSL4038 130°C/27°C 4 LEAD WYE 600V-
- 3 0.8 60 900 1125 1083 2850 574RSS4280 125°C/40°C 4 LEAD WYE 4160V 3 0.8 60 900 1125 156 1950 741FSM4360 130°C/27°C 6 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz k W k VA AMPS sk VA@30% Voltage Dip Generator Model- .. Temp Rise Connection 208V 3 0.8 60 800 1000 2776 2600 741RSL4045 105°C/40°C 12 LEAD LOW WYE 240V 3 0.8 60 800 1000 2406 2600 741RSL4045 105°C/40°C 12 LEAD HI DELTA 480V 3 0.8 60 800 1000 1203 2600 574RSL4037 105°C/40°C 12 LEAD HI WYE 600V 3 0.8 60 800 1000 962 2850 574RSS4280 105°C/40°C 4 LEAD WYE 4160V 3 0.8 60 800 1000 139 1950 741FSM4360 105°C/40°C 6 LEAD WYE
- The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
- - UL2200 Offered
// / /
Facts
// // // // // // // // // //
EPA Tier 2 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and factory tested MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty Custom Design for Any Application 16V-2000 G84 Diesel Engine
- 31.8 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
// //
//
//
plete Range of Accessories Permanent Magnet Generator (PMG)
- Brushless,...