• Part: DR-RDN20
  • Description: 20A Power Supply Redundancy Module
  • Manufacturer: MEAN WELL
  • Size: 115.92 KB
Download DR-RDN20 Datasheet PDF
MEAN WELL
DR-RDN20
DR-RDN20 is 20A Power Supply Redundancy Module manufactured by MEAN WELL.
20A Power Supply Redundancy Module - Features : ‧Suitable for redundant operation of 24V system ‧Installed on DIN Rail TS35 / 7.5 or 15 ‧Relay contact signal output and LED indicator for input failure alarm ‧Cooling by free air convection ‧3 years warranty SPECIFICATION MODEL REVERSE VOLTAGE (max.) OUTPUT OUTPUT CURRENT (max.) VOLTAGE DROP LED INDICATORS INPUT VOLTAGE RANGE INPUT NUMBER OF INPUTS INPUT CURRENT (max.) FUNCTION INPUT VOLTAGE ALARM WORKING TEMP. ENVIRONMENT WORKING HUMIDITY STORAGE TEMP., HUMIDITY VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 2) EMC EMISSION EMC IMMUNITY MTBF OTHERS DIMENSION PACKING NOTE DR-RDN20 30V 20A 0.6V Two green LEDs indicating each input is "OK or fail" 21 ~ 28V Two 20A per input When input is > 20V(± 5%) or < 30V(±5%) relay contacts -40 ~ +70℃ 20 ~ 90% RH non condensing -40 ~ +85℃, 10 ~ 95% RH 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mouning: pliance to IEC60068-2-6 UL508 approved Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC Terminal-Chassis :>100M Ohms / 500VDC / 25℃/ 70% RH pliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 pliance to EN61000-4-2,3,4,5,6,8,11, heavy industry level, criteria A 996.8Khrs min. MIL-HDBK-217F (25℃ ) 55.5- 125.2- 100mm (W- H- D) 0.5Kg; 20pcs/11Kg/1.29CUFT RELAY CONTACT RATING (max.) 30VDC, 1A 1. All parameters NOT specially mentioned are measured at 24VDC input, rated load and 25 ℃ of ambient temperature. 2. The power supply is considered a ponent which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of ponent power supplies.” (as available on http://.meanwell.) Typical Application Notes 1. 1+1 Redundancy Using 1 more PSU as the redundant unit PSU PSU 2. 1+N Redundancy: Using more PSUs as the redundant units to increase the...