Datasheet Summary
H Series
50 Watt AC-DC Converters
Input voltage range 85...255 V AC 1, 2 or 3 isolated outputs up to 48 V DC 4 kV AC I/O electric strength test voltage
- Rugged electrical and mechanical design
- Output 1 regulated, outputs 2 and 3 tracking
- Operating ambient temperature range
- 10...50 °C with convection cooling
Selection chart
Output 1 Output 2 Output 3 Rated power
Uo nom
[V DC] 5.1 12 15 24 48 12 15 5.1 5.1
Io nom
[A] 11 6 4.5 3 1.5 2 1.7 5 5
Uo nom
[V DC] 12 15 12 15
Io nom
[A] 2 1.7 0.7 0.6
Uo nom
[V DC] 12 15
Io nom
[A] 0.7 0.6
Po tot
[W] 56 72 67 72 72 48 51 42 43
Type Input voltage 85...255 V AC LH 1001-2R LH 1301-2R LH 1501-2R LH 1601-2R LH 1901-2R LH 2320-2 LH...