Click to expand full text
AC-DC
80-240 Watts DRS80-240 Series
xppower.com
• Ultra Slim Cases • 150% Peak Load for 4 seconds • Wide Output Adjustment Range • High Efficiency – Up to 92% • 12 V, 24 V & 48 V Versions • Low Output Ripple & Noise • -20 ºC to 70 ºC Operating Temperature
Specification
Input
Input Voltage
• 85-264 VAC
Input Frequency
• 47-63 Hz
Input Current
• 80 W: 2 A at 85 VAC 120 W: 2 A at 85 VAC 240 W: 4 A at 85 VAC
Inrush Current
• 30 A max at 230 VAC
Power Factor
• DRS80 0.6 typical DRS120 & 240 0.95 typical Conforms to EN61000-3-2 Class A.
Earth Leakage Current • 1.