GAS Engine-Generator Set 60-GC6NLT1 60 ekW 60 Hz Standby
/ /
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz Natural Gas Ratings: Amps Natural Gas Ratings: kW/kVA LP Gas Ratings: Amps LP Gas Ratings: kW/kVA skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 229 55/55 250 60/60 127 362CSL1606 130°C/27°C
12 LEAD ZIG-ZAG
240V** 1 1.0 60 229 55/55 250 60/60 230 362CSL1615 125°C/40°C
4 LEAD
208V** 3 0.8 60 208 60/75 208 60/75 148 361CSL1602 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 180 60/75 180 60/75 148 361CSL1602 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 90 60/75 90 60/75 142 361CSL1601 130°C/27°C
12 LEAD HI WYE
600V** 3 0.