Overview: Field Devices Europe
STD100 Duct Temperature Sensor NTC 1.8 kW for Vista 1 The STD100 temperature sensor is intended for air duct mounting.The STD100 housing is equipped with a 20 mm cable fitting. Technical DatA
Part numbers. . . . . . . . . . . . . . . . . . . . . . see table Sensor element. . . . NTC, 1.8 kΩ at +25 °C (77 °F) Time constant: Air velocity 1.5 m/s . . . . . . . . . . . . . . . approx. 72 s Air velocity 3.0 m/s . . . . . . . . . . . . . . . approx. 52 s Materials: Immersion tube . . . . . . . . . . . . . . . . stainless steel Connection box. . . . . . . . . . . . . . . polyamid plastic Mounting flange. . . . . . . . . . . . . . . . . . . aluminium Enclosure rating. . . . . . . . . . . . . . . . . . . . . . . IP 65 Dimensions. . . see table below and figure overleaf Accuracy. . . . . . . . . . . . . . . . . . . . . . . . . see table Temperatures: Ambient. . . . . . . . . . . . . . . . . . min. -40°C (-40 °F) . . . . . . . . . . . . . . . . . . . . . . . .max. 130°C (266 °F) Operating. . . . . . . . . . . . . . . . . min. -40°C (-40 °F) . . . . . . . . . . . . . . . . . . . . . . . .max. 150°C (302 °F) Standards: EMC. . . . . . . . . . . . . . . . EN 50081-1, EN 50082-1 ACCURACY
At Temperature –25 °C/–13 °F ±0 °C/32 °F 25 °C/77 °F 50 °C/122 °F 75 °C/167 °F 100 °C/212 °F Accuracy ±0.7 °C/±1.3 °F ±0.5 °C/±0.9 °F ±0.3 °C/±0.5 °F ±0.6 °C/±1.1 °F ±0.9 °C/±1.6 °F ±1.3 °C/±2.3 °F Field Devices Europe STD100 DIMENSIONS (mm/in)
84 (3.31) 65 (2.56) M20x1.5 44 (1.73) 65 (2.56) 30 (1.18) 30 (1.18) 6 (0.24) 2 NL DUCT MOUNTING (mm/in)
M4 8 (0.31) 13 (0.5) 2.7 (0.11) 40 (1.57) 33 (1.3)
15 (0.59) 6.2 (0.25) 4.5 (0.