Click to expand full text
2 Hanbury Road Chelmsford Essex CM1 3AE United Kingdom
T: +44 (0)1245-809110 F: +44 (0)1245-809112 E: sales.is@sgxsensortech.com www.sgxsensortech.com
SGX-7H2S Datasheet Industrial Hydrogen Sulfide Sensor
Application : Fixed Gas Detectors
PERFORMANCE
Typical Baseline Range…..<±0.5 ppm H2S equivalent Measurement Range ……...………………. 0 – 50 ppm Output Signal ……………...…… 1700 ± 400 nA / ppm Linearity …………………....…. .…………………. Linear Repeatability …………………...< ±1% H2S equivalent Response time, t90 ……….…. …………………... <40 s Maximum Overload …….…….………………. 500 ppm Long-term output drift …….…….……… <5% per annum Recommended Load Resistor ………….……... 10 ohms Warranty ………………………. .…………………. 2 year Resolution (Electronics dependent) ……….. < 0.1 ppm typical
OPERATING CONDITIONS
Temperature Range ….….…. ..